Subscription / Get Once |
LID Name |
LID Number |
Type |
Sim File Name |
Description |
X |
INVALID_LID_NUMBER |
0 |
X |
|
|
Unique |
ILID_LAST_BLURT_REAL_TIME_IN_MS |
18153640 |
Uint64 |
|
Last time at which all energy quantities were updated, in UTC 1970 time in milliseconds. |
Sub |
ILID_INS_CURRENT_A |
18153515 |
Double |
Amp A |
One second RMS current on phase A, in amps. Resolution of 3.23688 microamps. |
Sub |
ILID_INS_CURRENT_B |
18153516 |
Double |
Amp B |
One second RMS current on phase B, in amps. Resolution of 3.23688 microamps. |
Sub |
ILID_INS_CURRENT_C |
18153517 |
Double |
Amp C |
One second RMS current on phase C, in amps. Resolution of 3.23688 microamps. |
Sub |
ILID_INS_FREQUENCY |
18153518 |
Double |
Frequency |
Number of cycles per second measured on the line side. Resolution is 1cycle. |
Sub |
ILID_INS_VOLTS_A |
18153520 |
Double |
Volt A |
One second RMS voltage on phase A, in volts. Resolution of 1decivolt BLURT or 2.5 centivolts CPC. |
Sub |
ILID_INS_VOLTS_B |
18153521 |
Double |
Volt B |
One second RMS voltage on phase A, in volts. Resolution of 1decivolt BLURT or 2.5 centivolts CPC. |
Sub |
ILID_INS_VOLTS_C |
18153522 |
Double |
Volt C |
One second RMS voltage on phase A, in volts. Resolution of 1decivolt BLURT or 2.5 centivolts CPC. |
Sub |
ILID_INS_VAS_AGGREGATE |
18153530 |
Double |
VA |
One second average of apparent power across all phases, in volt-ampere (VA). Resolution of 8.28641 milliVA. |
Sub |
ILID_INS_WATTS_AGGREGATE |
18153531 |
Double |
Watt |
One second average of power across all phases, in watts. Resolution of 8.28641 milliwatts. |
Sub |
ILID_INS_VAR_AGGREGATE |
18153532 |
Double |
VAR |
One second average of reactive power across all phases, in volt-ampere reactive (VAR). Resolution of 8.28641 milliVAR. |
Sub |
ILID_INS_TEMPERATURE_CELCIUS |
18153533 |
Double |
Temperature |
Heat measured by the metrological temperature sensor, measured in degrees celcius. Resolution of 1 degree. |
Sub |
ILID_INS_POWER_FACTOR |
18153559 |
Double |
PowerFactor |
The ratio of real power vs apparent power, a unit-less number. Ranges from -1 to 1. |
Sub |
ILID_INS_VAB_ANGLE |
18153644 |
Double |
V-Angle A-B |
The phase shift between phase A voltage and phase B voltage, in degrees. Resolution is 1 decidegree. |
Sub |
ILID_INS_VAC_ANGLE |
18153645 |
Double |
V-Angle A-C |
The phase shift between phase A voltage and phase C voltage, in degrees. Resolution is 1 decidegree. |
Sub |
ILID_NEUTRAL_CURRENT_MEASURED |
18153652 |
Double |
Amp N-Measured |
One second RMS current on the meter neutral, in amps. Resolution of 3.23688 microamps. |
Sub |
ILID_NEUTRAL_CURRENT_CALCULATED |
18153653 |
Double |
Amp N-Calculated |
One second RMS current for all phases (A+ -B+C = neutral), in amps. Resolution of 3.23688 microamps. |
Sub |
ILID_NEUTRAL_CURRENT_TAMPER |
18153654 |
Double |
Amp N-Tamper |
One second RMS current calculated from ILID_NEUTRAL_CURRENT_CALCULATED -ILID_NEUTRAL_CURRENT_MEASURED, in amps. Is a measure of theft, tamper or other physical anomaly. Resolution of 3.23688 microamps. |
Sub |
ILID_INS_VA_PHA |
18153655 |
Double |
VA A |
One second average of apparent power for phase A, in volt-ampere (VA). Resolution of 8. -28641 milliVA. |
Sub |
ILID_INS_VA_PHB |
18153656 |
Double |
VA B |
One second average of apparent power for phase B, in volt-ampere (VA). Resolution of 8. -28641 milliVA. |
Sub |
ILID_INS_VA_PHC |
18153657 |
Double |
VA C |
One second average of apparent power for phase C, in volt-ampere (VA). Resolution of 8. -28641 milliVA. |
Sub |
ILID_INS_W_PHA |
18153658 |
Double |
Watt A |
One second average of power for phase A, in watts. Resolution of 8.28641 milliwatts. |
Sub |
ILID_INS_W_PHB |
18153659 |
Double |
Watt B |
One second average of power for phase B, in watts. Resolution of 8.28641 milliwatts. |
Sub |
ILID_INS_W_PHC |
18153660 |
Double |
Watt C |
One second average of power for phase C, in watts. Resolution of 8.28641 milliwatts. |
Sub |
ILID_INS_VAR_PHA |
18153661 |
Double |
VAR A |
One second average of reactive power on phase A, in volt-ampere reactive (VAR). Resolution of 8.28641 milliVAR. |
Sub |
ILID_INS_VAR_PHB |
18153662 |
Double |
VAR B |
One second average of reactive power on phase B, in volt-ampere reactive (VAR). Resolution of 8.28641 milliVAR. |
Sub |
ILID_INS_VAR_PHC |
18153663 |
Double |
VAR C |
One second average of reactive power on phase C, in volt-ampere reactive (VAR). Resolution of 8.28641 milliVAR. |
Sub |
ILID_CPC_DATA_INSTLOADVOLTAGEPHA |
18153795 |
Double |
Volt LS A |
One second RMS voltage on load side of phase A, in volts. CPC only. Resolution of 2.5 centi-volts. |
Sub |
ILID_CPC_DATA_INSTLOADVOLTAGEPHB |
18153796 |
Double |
Volt LS B |
One second RMS voltage on load side of phase B, in volts. CPC only. Resolution of 2.5 centi-volts. |
Sub |
ILID_CPC_DATA_INSTLOADVOLTAGEPHC |
18153797 |
Double |
Volt LS C |
One second RMS voltage on load side of phase C, in volts. CPC only. Resolution of 2.5 centi-volts. |
Sub |
ILID_INS_CURRENT_ANGLE_PHA |
18153839 |
Double |
I-Angle A |
The phase shift between phase A current and phase A voltage, in degrees. Resolution is 1decidegree. |
Sub |
ILID_INS_CURRENT_ANGLE_PHB |
18153840 |
Double |
I-Angle B |
The phase shift between phase B current and phase A voltage, in degrees. Resolution is 1decidegree. |
Sub |
ILID_INS_CURRENT_ANGLE_PHC |
18153841 |
Double |
I-Angle C |
The phase shift between phase C current and phase A voltage, in degrees. Resolution is 1decidegree. |
Get 1 |
ILID_INSTRUMENTDATA_RATED_VOLTAGE |
18153619 |
Uint16 |
|
The maximum supported voltage value of this meter, in volts. |
Get 1 |
ILID_INSTRUMENTDATA_RATED_CURRENT |
18153620 |
Uint16 |
|
The maximum supported current value of this meter, in amps. |
Get 1 |
ILID_BASE_METER_FORM |
18153550 |
Uint8 |
|
Enumeration that represents the expected electrical configuration of the meter. See Meter Form Enumeration. |
Get 1 |
ILID_BASE_METER_NUMBER_PHASES |
18153557 |
Uint8 |
|
The number of phases supported by this meter's metrology base. |
Get 1 |
ILID_INSTRUMENTSETTINGS_VOLTAGE_TFMR_NUMERATOR |
18153610 |
Uint32 |
|
For a transformer rated meter, the numerator of the transformer voltage ratio. |
Get 1 |
ILID_INSTRUMENTSETTINGS_VOLTAGE_TFMR_DENOMINATOR |
18153613 |
Uint32 |
|
For a transformer rated meter, the denominator of the transformer voltage ratio. |
Get 1 |
ILID_PHASE_A_NOMINAL_VOLTAGE |
18153832 |
Double |
|
The expected voltage level on phase A for this particular meter, in volts. |
Get 1 |
ILID_PHASE_B_NOMINAL_VOLTAGE |
18153833 |
Double |
|
The expected voltage level on phase B for this particular meter. |
Get 1 |
ILID_PHASE_C_NOMINAL_VOLTAGE |
18153834 |
Double |
|
The expected voltage level on phase C for this particular meter. |
Get 1 |
ILID_BASE_METER_TYPE |
18153836 |
Uint8 |
|
Enumeration that represents the physical configuration of the meter. See Meter Type Enumeration |
Meter Form Enumeration
Value |
Standard Electric Meter Form Number |
0 |
1 |
1 |
2 |
2 |
3 |
3 |
4 |
4 |
9 |
5 |
10 |
6 |
12 |
7 |
13 |
8 |
16 |
9 |
25 |
10 |
29 |
11 |
36 |
12 |
45 |
13 |
46 |
14 |
48 |
15 |
56 |
16 |
66 |
17 |
96 |
Meter Type Enumeration
Value |
Definition |
0 |
Unspecified Base |
1 |
S Base |
2 |
A Base |
3 |
K Base |
4 |
IEC Base |
5 |
Switch Base |
6 |
Rack Base |
7 |
B Base |
8 |
P Base |
9 |
IEC Symmetric Base |